Altronix : EFLOW104N8
Power Supply/Charger w/Fire Alarm Disconnect – 24VDC @ 10 amp max
By: Altronix
Low Voltage Electronics and Power Solutions.
Description
The Altronix eFlow104N8 is a power supply/charger that converts a 120VAC 60Hz input into eight (8) fuse protected 24VDC outputs with a total of 10 amps max. The unit includes an unswitched aux. output. It also offers a suite of features that includes fire alarm disconnect, over voltage protection, and low power disconnect which prevents deep discharge of stand-by batteries.
Available Configurations Include:
EFLOW104N16 | Power Supply/Charger w/Fire Alarm Disconnect – 24VDC @ 10 amp max. Sixteen (16) fused outputs and one (1) aux. power output, AC & battery monitoring, Low battery cutoff, Over voltage protection, encl. 13.5”H x 13”W x 3.25”D accomodates up to (2) 12VDC/7AH batteries, 115VAC input, UL Listed (UL294/UL603/UL1481), cUL Listed (ULC-S318-96). CSFM, CE Approved. |
EFLOW104NX8 | Power Supply/Charger w/Fire Alarm Disconnect – 24VDC @ 10 amp max. Eight (8) fused outputs and one (1) aux. power output, AC & battery monitoring, Low battery cutoff, Over voltage protection, encl. 15.5”H x 12”W x 4.5”D accomodates up to (2) 12VDC/12AH batteries, 115VAC input, UL Listed (UL294/UL603/UL1481), cUL Listed (ULC-S318-96). CSFM, CE Approved. |
EFLOW104NX16 | Power Supply/Charger w/Fire Alarm Disconnect – 24VDC @ 10 amp max. Sixteen (16) fused outputs and one (1) aux. power output, AC & battery monitoring, Low battery cutoff, Over voltage protection, encl. 15.5”H x 12”W x 4.5”D accomodates up to (2) 12VDC/12AH batteries, 115VAC input, UL Listed (UL294/UL603/UL1481), cUL Listed (ULC-S318-96). CSFM, CE Approved. |
Features
EFLOW104N8 features include:
- 120VAC, 60Hz, 4.5 amp.
- Input fuse: 5A/250V.
- Eight (8) fuse protected outputs.
- Outputs are rated @ 2.5 amp.
- 24VDC @ 10.0 amp supply current.
- Auxiliary Power-Limited output rated @ 1 amp (unswitched).
- Over Voltage Protection.
- Built-in charger for sealed lead acid or gel type batteries.
- Maximum charge current 1.54 amp.
- Automatic switch over to stand-by battery when AC fails. Transfer to stand-by battery power is instantaneous with no interruption.
- AC fail supervision (form "C" contacts).
- Battery fail & presence supervision (form "C" contacts).
- Low power shutdown. Shuts down DC output terminals if battery voltage drops below 70-75% (depending on the power supply). Prevents deep battery discharge.
- Supervised Fire Alarm disconnect (latching or non-latching) 10K EOL resistor. Operates on a normally open (NO) or normally closed (NC) trigger.
- Operating temperature: 0° C to 49° C ambient.
- BTU/Hr.: 124.85 BTU/Hr.
- System AC input VA requirement: 540VA.
- Green AC Power LED indicates 120VAC present.
- AC input, DC output and Battery LED indicators.
- Short circuit and overload protection.
- Unit is complete with power supply, enclosure, battery leads and cam lock.
Resources & Documents
eflow104n8.pdf | Datasheet |