5 Output Power Supply/Charger w/Fire Alarm Disconnect – 12VDC @ 10 amp
Low Voltage Electronics and Power Solutions.

Altronix : AL1012ULM
Description
The Altronix AL1012ULM multi-output access control power supply/charger is specifically designed for use with access control systems and accessories. This unit converts a 115VAC, 60Hz input into five (5) individually protected Class 2 Rated power limited 12VDC outputs. Each output will route power to a variety of access control hardware devices including Mag Locks, Electric Strikes, Magnetic Door Holders, etc. These outputs will operate in both Fail-Safe and Fail-Secure modes. Controlled trigger input is achieved through normally open (N.O.) or normally closed (N.C.) supervised input or the polarity reversal from an FACP (Fire Alarm Control Panel). A form “C” dry output relay enables HVAC Shutdown, Elevator Recall orit may be used to trigger auxiliary devices.
Available Configurations Include:
AL1024ULM | 5 Output Power Supply/Charger w/Fire Alarm Disconnect – 24VDC @ 10 amp, PTC Class 2 power-limited outputs, encl. 13.5″H x 13″W x 3.25″D., 115VAC input, UL Listed (UL294/UL1481), cUL Listed, CSFM & MEA Approved. |
AL1024ULMR | 5 Output Power Supply/Charger w/Fire Alarm Disconnect – 24VDC @ 10 amp, PTC Class 2 power-limited outputs, red encl. 13.5″H x 13″W x 3.25″D., 115VAC input, UL Listed (UL294/UL1481), cUL Listed, CSFM & MEA Approved. |
Features
AL1012ULM features include:
- Input 115VAC, 60Hz, 2.6 amp.
- Input fuse rated @ 3.5 amp/250V.
- Fire Alarm Panel or Access Control System trigger inputs. N.O. or N.C. supervised trigger input and polarity reversal trigger input.
- 12VDC outputs.
- 10 amp supply current.
- Five (5) PTC protected Class 2 Rated power limited outputs, rated @ 2 amp.
- Output relay energizes when unit is triggered (form "C" contact rated 1 amp @ 28VDC).
- Filtered and electronically regulated output.
- Short circuit and thermal overload protection.
- Built-in charger for sealed lead acid or gel type batteries.
- Automatic switch over to stand-by battery when AC fails.
- Maximum charge current 0.7 amp.
- AC fail supervision (form "C" contacts).
- Low battery supervision (form "C" contacts).
- Battery presence supervision (form "C" contacts).
- Power fail supervision relay (form "C" contacts).
- AC input and DC output LED indicators (power supply board).
- Red LEDs indicate condition of power outputs (multi-output board).
- Power & input trigger LEDs (multi-output board).
- Operating temperature: 0° C to 49° C ambient.
- 61.42 BTU/Hr.
- System AC input VA requirement: 299VA.
Resources & Documents
al1012ulm.pdf | Datasheet |