5 Output Power Supply/Charger w/Fire Alarm Disconnect - 12VDC @ 10 amp

Contact us for lowest price (800) 284-2288 , (858) 565-1101 Call Now [email protected]

The Altronix AL1012ULM multi-output access control power supply/charger is specifically designed for use with access control systems and accessories. This unit converts a 115VAC, 60Hz input into five (5) individually protected Class 2 Rated power limited 12VDC outputs. Each output will route power to a variety of access control hardware devices including Mag Locks, Electric Strikes, Magnetic Door Holders, etc. These outputs will operate in both Fail-Safe and Fail-Secure modes. Controlled trigger input is achieved through normally open (N.O.) or normally closed (N.C.) supervised input or the polarity reversal from an FACP (Fire Alarm Control Panel). A form "C" dry output relay enables HVAC Shutdown, Elevator Recall orit may be used to trigger auxiliary devices.

 

Available Configurations Include:

AL1024ULM 5 Output Power Supply/Charger w/Fire Alarm Disconnect - 24VDC  @ 10 amp, PTC Class 2 power-limited outputs, encl. 13.5"H x 13"W x 3.25"D., 115VAC input, UL Listed (UL294/UL1481), cUL Listed, CSFM & MEA Approved.
AL1024ULMR 5 Output Power Supply/Charger w/Fire Alarm Disconnect - 24VDC  @ 10 amp, PTC Class 2 power-limited outputs, red encl. 13.5"H x 13"W x 3.25"D., 115VAC input, UL Listed (UL294/UL1481), cUL Listed, CSFM & MEA Approved.

 

AL1012ULM features include:

  • Input 115VAC, 60Hz, 2.6 amp.
  • Input fuse rated @ 3.5 amp/250V.
  • Fire Alarm Panel or Access Control System trigger inputs. N.O. or N.C. supervised trigger input and polarity reversal trigger input.
  • 12VDC outputs.
  • 10 amp supply current.
  • Five (5) PTC protected Class 2 Rated power limited outputs, rated @ 2 amp.
  • Output relay energizes when unit is triggered (form "C" contact rated 1 amp @ 28VDC).
  • Filtered and electronically regulated output.
  • Short circuit and thermal overload protection.
  • Built-in charger for sealed lead acid or gel type batteries.
  • Automatic switch over to stand-by battery when AC fails.
  • Maximum charge current 0.7 amp.
  • AC fail supervision (form "C" contacts).
  • Low battery supervision (form "C" contacts).
  • Battery presence supervision (form "C" contacts).
  • Power fail supervision relay (form "C" contacts).
  • AC input and DC output LED indicators (power supply board).
  • Red LEDs indicate condition of power outputs (multi-output board).
  • Power & input trigger LEDs (multi-output board).
  • Operating temperature: 0° C to 49° C ambient.
  • 61.42 BTU/Hr.
  • System AC input VA requirement: 299VA.
al1012ulm.pdfDatasheet